Schneider Easy UPS 3S
10 – 40 kVA 3-phase UPS
10-40kVA, 208/400V easy-to-install, easy-to-use, and easy-to-service 3 phase UPS for small and medium data centers and other business critical applications.
The Schneider Electric Easy UPS 3S supplies power stability with robust electrical specifications and long-lasting performance to ensure your business continuity. Designed for fast and easy installation in the data center or electrical room, this EcoStruxure connected UPS features a wide operating temperature window and strong overload protection, all in a compact and lightweight footprint. With its exceptional combination of advanced product features, competitive specifications and ease of installation, use, and service, the Schneider Electric Easy UPS 3S is the easy choice for your business continuity.
ECO Mode
Operating mode that by-passes unused electrical components in good power conditions to achieve high operating efficiency without sacrificing protection
Easy to install fast
Quickly roll the compact and lightweight UPS into position.
Easy Loop Test
Verifies UPS performance before you connect your load, without the need for a load bank.
Straightforward installation
Including the input, output, and bypass breakers, as well as the Emergency Power Off (EPO) switch, simplifies installation planning and speeds up deployment.
Intuitive user interface
The intuitive graphical user interface allows for easy system configuration.
Front-access servicing
Simplifies installation and UPS maintenance while minimizing space requirements.
Wide Input Voltage Window
Saves your battery power for when you really need it – during power cuts!
Replaceable dust filters
protect the UPS in harsh environments.
Parallel capability
Multiple units can be placed in parallel to meet power capacity and redundancy requirements
Optional SNMP Card
When you purchase the SNMP card, you can monitor and manage UPS status remotely through the UPS Web interface or through EcoStruxure IT’s cloud-based and on-premise software suites.
Power Rating (kVA/kW) | |||||
Easy UPS 3:1 | 10/10 | 15/15 | 20/20 | 30/30 | |
Easy UPS 3:3 | 10/10 | 15/15 | 20/20 | 30/30 | 40/40 |
Normal AC supply input | |||||
Input voltage (V) | 380/400/415 V (Three-phase + Neutral) | ||||
Frequency (Hz) | 45 – 65 Hz | ||||
Input power factor | >0.99 | ||||
THDI | <3% for 10 kVA UPS, <4% for 15-40 kVA UPS | ||||
Input voltage range | 304 V to 477 V at full load | ||||
Dual mains input | Yes (default: single mains input) | ||||
Output | |||||
Nominal output voltage (V) | 3:1 – 220/230/240 V | ||||
3:3 – 380/400/415 V | |||||
Efficiency: Double conversion mode | Up to 96% | ||||
Efficiency: ECO mode | Up to 99% | ||||
Overload capacity in normal operation | 130% for 10 minutes and 130-150% for one minute | ||||
Output voltage tolerance | +/-1% | ||||
Communication and management | |||||
Communication interface | RS232, RS485, USB, dry contact, Modbus TCP/IP, optional network card | ||||
Control panel | Multi-function LCD, status and display console | ||||
Weights and dimensions | |||||
UPS for external batteries, unpackaged/ shipping dimensions (H × W × D, mm) |
530 × 250 × 700 mm/ 772 × 400 × 857 mm |
530 × 250 × 700 mm/ 772 × 400 × 857 mm |
770 × 250 × 800 mm/ 1015 × 400 × 982 mm |
770 × 250 × 800 mm/ 1015 × 400 × 982 mm |
770 × 250 × 900 mm/ 1015 × 400 × 1050 mm |
UPS for internal batteries, without batteries, unpackaged/ shipping dimensions (H x W x D, mm) |
1400 × 380 × 928 mm/ 1640 × 563 × 1014 mm |
1400 × 380 × 928 mm/ 1640 × 563 × 1014 mm |
1400 × 380 × 928 mm/ 1640 × 563 × 1014 mm |
1400 × 500 × 969 mm/ 1640 × 683 × 1114 mm |
1400 × 500 × 969 mm/ 1640 × 683 × 1114 mm |
UPS for external batteries, unpackaged/shipping weight (kg) |
36/50 | 36/50 | 58/75 | 60/77 | 70/86 |
UPS for internal batteries, without batteries, unpackaged/shipping weight (kg) |
112/145 | 112/145 | 122/158 | 152/190 | 158/195 | Battery string (1 string/4 modules), unpackaged/shipping weight (kg) |
27 kg per module/28 kg per module |
Regulatory | |||||
Safety | IEC/EN62040-1-1 | Performance | IEC 62040-3 | ||
EMC/EMI/RFI | IEC 62040-2 | Environmental | IEC 62040-4 | ||
Markings | CE.RCM, EAC, WEEE | ||||
Battery type | |||||
Battery type | VRLA | ||||
Nominal DC bus (100% load) | +/-192 to +/-240 | ||||
Charging power in % of output power (selectable) |
1-20% | ||||
Environmental | |||||
Operating temperature | 0°C to 40°C | ||||
Relative humidity | 0 to 95% non-condensing | ||||
Operating elevation | 0 to 1,000 m at 100% load | ||||
Audible noise at 1 m from unit | 10-20 kVA: 60 dBA at 100% load; 30-40 kVA: 63 dBA at 100% load | ||||
Protection class | IP20 | ||||
Warranty | One year with Schneider Electric-certified Field Service Representative or Certified Service Partner Start-up Service (sold separately) |