60 – 200 kVA 3-phase UPS

60 – 200kVA, 400V easy-to-install, easy-to-connect, easy-to-use, and easy-to-service 3 phase UPS for small and medium data centers and other business critical applications.

The Schneider Electric Easy UPS 3M, part of the 3 phase Easy UPS series, is an easy-to-install, easy-to-connect, easy-to-use, and easy-to-service 60-200kVA 3 phase UPS ideal for small and medium data centers and other business critical applications. Easy UPS 3M supplies power stability and long-lasting performance with advanced product features, robust electrical specifications and compact design to ensure your business continuity.

Designed for fast and easy installation in the data center or electrical room, this EcoStruxure-ready UPS features a wide operating temperature window and strong overload protection, all in a lightweight footprint. With its exceptional combination of low Total Cost of Ownership, competitive specifications, and ease of use, the Schneider Electric Easy UPS 3M is the easy choice for your business continuity in the data center or electrical room. Start-up service is included to optimize your system’s performance, quality, and safety.

ECO Mode
Operating mode that by-passes unused electrical components in good power conditions to achieve high operating efficiency without sacrificing protection

Easy to install fast
Quickly roll the compact and lightweight UPS into position.

Easy Loop Test
Verifies UPS performance before you connect your load, without the need for a load bank.

Straightforward installation
Including the input, output, and bypass breakers, as well as the Emergency Power Off (EPO) switch, simplifies installation planning and speeds up deployment.

Front-access servicing
Simplifies installation and UPS maintenance while minimizing space requirements.

Wide Input Voltage Window
Saves your battery power for when you really need it – during power cuts!

Replaceable dust filters
protect the UPS in harsh environments.

Parallel capability
Multiple units can be placed in parallel to meet power capacity and redundancy requirements

Optional SNMP Card
When you purchase the SNMP card, you can monitor and manage UPS status remotely through the UPS Web interface or through EcoStruxure IT’s cloud-based and on-premise software suites.

Power Rating (kVA/kW) 60/60 80/80 100/100 120/120 160/160 200/200
Normal AC supply input
Input voltage (V) 380/400/415 V (Three-phase + Neutral)
Frequency (Hz) 40-70 Hz
Input power factor >0.99
THDI <3% at full linear load
Input voltage range 342 V to 477 V at full load at 40°C**
Dual mains input Yes (default: single mains input)
Output
Nominal output voltage (V) 3:3 – 380/400/415 V
Efficiency: Double
conversion mode
Up to 95.5%
Efficiency: ECO mode Up to 99%
Overload capacity in
normal operation
125% for 10 minutes, 150% for 1 minute*
Output voltage tolerance +/-1%
Communication and management
Communication interface RS485, USB, Dry contact, Modbus TCP/IP (SNMP optional)
Control panel Five inch touchscreen LCD, status, and display console
Weights and dimensions
UPS for external batteries,
unpackaged/ shipping
dimensions (H × W × D, mm)
915 × 360 × 850 mm/
1140 × 475 × 965 mm
915 × 360 × 850 mm/
1140 × 475 × 965 mm
915 × 360 × 850 mm/
1140 × 475 × 965 mm
1300 × 500 × 850 mm/
1500 × 625 × 975 mm
1300 × 500 × 850 mm/
1500 × 625 × 975 mm
1300 × 600 × 850 mm/
1500 × 725 × 975 mm
UPS with internal batteries,
unpackaged/shipping
dimensions (HxWxD, mm)
1970 × 600 × 1000mm/
2102 × 750 × 1125mm
1970 × 600 × 1000mm
2102 × 750 × 1125mm
UPS for external batteries,
unpackaged/shipping,
weights (kg)
109/133 140/164 145/169 193/223 227/257 304/338
UPS for internal batteries,
without batteries,
unpackaged/shipping
weight (kg)
311/360 339/387
Regulatory
Safety IEC/EN 62040-1 Performance IEC 62040-3
EMC/EMI/RFI IEC 62040-2 Environmental IEC 62040-4
Markings CE TUV
Battery type
Battery type VRLA
Nominal DC bus (100% load) +/-216 to +/-300
Charging power in % of
output power (selectable)
for external
batteries: 1-20%
with internal
batteries: 1-16%
for external
batteries: 1-30%
with internal
batteries: 1-24%
for external
batteries: 1-24%
for external
batteries: 1-20%
for external
batteries: 1-22.5%
for external
batteries: 1-24%
Environmental
Operating temperature 0°C to 40°C
Relative humidity 0 to 95% non-condensing
Operating elevation 0 to 1,500 m at 100% load
Audible noise at
1 m from unit
60-100 kVA: 65 dBA at 100% load*; 120-200 kVA: <70 dBA at 100% load*
Protection class IP20

*Under 30°C
**342–150 with a linear derating of the load to 30%